| Parametro | Valore |
|---|---|
| Stato | Active |
| ETIM 5.0 (DIMENSIONI) | EC000228 |
| ETIM 6.0 (DIMENSIONI) | EC000228 |
| Peso (SPECIFICHE) | 4.5 kg |
| Viaggi (STATO ORDINE/CONSEGNA) | Electronic Trip Unit without Rating Plug |
| Im (A) (STATO ORDINE/CONSEGNA) | 320-4550 A |
| In (A) (STATO ORDINE/CONSEGNA) | 350 A |
| Ir (A) (STATO ORDINE/CONSEGNA) | 160-350 A |
| Serie (STATO ORDINE/CONSEGNA) | Circuit breaker (complete breaker) |
| Ui (V) (STATO ORDINE/CONSEGNA) | 750 V |
| NEMA 240V (STATO ORDINE/CONSEGNA) | 100 kA |
| NEMA 480V (STATO ORDINE/CONSEGNA) | 50 kA |
| Unità di viaggio (STATO ORDINE/CONSEGNA) | Motor & Line & Generator protection (SMR2) |
| Tipo di frame (STATO ORDINE/CONSEGNA) | G frame (400A/630A) |
| IEC 230VAC (STATO ORDINE/CONSEGNA) | 90 kA |
| IEC 400VAC (STATO ORDINE/CONSEGNA) | 50 kA |
| IEC 440VAC (STATO ORDINE/CONSEGNA) | 42 kA |
| IEC 500VAC (STATO ORDINE/CONSEGNA) | 30 kA |
| IEC 690VAC (STATO ORDINE/CONSEGNA) | 10 kA |
| Misure (STATO ORDINE/CONSEGNA) | 262x138.7x123 mm |
| IEC 690VAC Ics (STATO ORDINE/CONSEGNA) | 10 kA |
| IEC 690VAC Icu (STATO ORDINE/CONSEGNA) | 10 kA |
| Numero di poli (STATO ORDINE/CONSEGNA) | 3P |
| Quadro di valutazione (A) (STATO ORDINE/CONSEGNA) | 400 A |
| Imballaggio standard (STATO ORDINE/CONSEGNA) | 1 |
| Per unità di viaggio - In (A) (STATO ORDINE/CONSEGNA) | 350 A |
| Capacità di cortocircuito (kA) (STATO ORDINE/CONSEGNA) | Normal 50 kA |
Specifiche tecniche e dati di prestazione
Guida di installazione e utilizzo